Timer configuration, Basic operations, Blinking) – IDEC FS1A Controller User Manual

Page 44

Advertising
background image

BASIC OPERATIONS

4-6

Timer configuration

SafetyOne has an OFF-delay timer function that retains safety outputs during the configured
time and after that turns OFF the safety outputs. You can use this function to configure stop
category "0" or "1". Perform the configuration procedure listed below to configure the
OFF-delay timer to one of the following eight settings, using the same procedure as that for
configuring the logic:
0, 0.1, 0.5, 1, 2, 5, 15 or 30 s.

Configuration operations are disabled in the Initial and Stop states.
Once any timer value is configured, it is kept in the SafetyOne even if the power is turned off.
Logic and timer settings can be configured at the same time. Confirm the configuration methods,
and configure the logic and timer properly.
The timer switch is set at a default value of “1(0s)” at the factory. When initially powering on the
SafetyOne, thoroughly confirm the configuration and the operation.

1. Open the protective cover.
Open the cover to a position that enables you to
set configuration operations.
Refer to "Using the protective cover" for details.

2. Select the timer switch.
Select and operate a timer switch. When
operating a timer switch, use the configuration
tool.
When the timer configuration is changed, "C" is
displayed in the error LED display and the timer
LED light that corresponds to the selected timer
configuration switch blinks.
















0 .1 .5 1 2 5 15 30

SAFE-IN

TIMER(S)

SAFE-OUT

SOLENOID
-OUT

START-IN

X0

X1

X2

X3

X4

X5

X6

X7

X10

X11

X12

X13

X14

X15

X16

X17

Y0

Y1

Y2

Y3

Y17

Y20

LOGIC ERROR

TYPE :

Fig. 4.7 Timer switch is not selected
(Configuration state)

Fig. 4.8 OFF-delay timer value “2s” is
selected (Configuration state)

(Blinking)

TYPE :

0 .1 .5 1 2 5 15 30

SAFE-IN

TIMER(S)

SAFE-OUT