Error detection function – IDEC FS1A Controller User Manual

Page 366

Advertising
background image

LOGIC

5-318

X

n

X

n+1

I

n

ON

OFF

Input monitor error
detection time:Max.0.1s

Independent conditon
change in one input

Y

m

(Monitor output)

SafetyOne changes to
Protection State after an input
monitor error is detected.

1Hz pulse signal is output from
corresponded monitor output.

0.5s

0.5s

ON

OFF

ON

OFF

ON

OFF

Cance-

llation

Fig. 5-8 Operation timing of a dual channel safety input function

Error detection function

Input monitoring and grounding detection
When an error is detected between the dual channel inputs, the SafetyOne changes to the
Protection state and displays "1" on the error LED display. The conditions to be detected as input
errors are shown below.

●When an input monitoring error detection time (0.1s) is exceeded during the 2 input conditions

and they do not match (namely ON/OFF or OFF/ON).

●When there is an independent condition change of 1 of the inputs.
●The input circuit of the ON state has gone to ground.

The input LEDs blink and the monitor output (Y

m

) supplies pulses (1Hz), to notify the operator of

the corresponding input. See Fig. 5-8.

Noise detection filter
The SafetyOne is tested acording to IEC/EN 61000-6-2, however in the case when the SafetyOne
is used in an environment with severe noise, the SafetyOne changes to the Stop state and displays
"9" on the error LED display.

Note. Drive circuit corresponding to the dual channel safety input (T

n

, T

n+1

) is always OFF.