IDEC FS1A Controller User Manual

Page 53

Advertising
background image

LOGIC

5-5

Chapter 5

Wiring example of a SafetyOne and a SafetyOne

Y0

X0

X1

T0

T1

Y1

Control category 4
MTTF

100 years

DC high
PL e

SafetyOne

1

SafetyOne

2

Dual Channel Safety

Y0

X0

X1

T0

T1

note:
Stopping the whole system by the safety output of
SafetyOne 1 is recommended.
(In case of a short circuit between Y0 and external
conductors, only SafetyOne 1 detects the error.)

Y1

Control category 3
MTTF

100 years

DC Medium
PL d

SafetyOne

1

SafetyOne

2

Dual Channel Safety

Note:
To avoid short circuit between each cable,
-Fix the cables permanently and protect against external
damage, e.g. by cable ducting, conduit.....
or
-Use individually shielded cables with earth connection.


Warning

Applicable safety performance depends on the whole system configuration.