Functions (logic 101) – IDEC FS1A Controller User Manual

Page 56

Advertising
background image

LOGIC

5-8

Functions (Logic 101)


●Safety inputs: X0 to X13 (T0 to T13)
Safety inputs are used to diagnose the status of connected safety devices, such as emergency stop
switches, and interlock switches.

Intended inputs
(Terminal names)

Function

Function name

Dual channel dependent input

Symbol

Dual Channel

D

epende nt

Description of operation

This function diagnoses the status of
connected safety devices. This function
does not diagnose the time interval of
status transition between each input of
duplicated inputs.

Safety input 1
(X0-T0, X1-T1)
Safety input 2
(X2-T2, X3-T3)
Safety input 3
(X4-T4, X5-T5)
Safety input 4
(X6-T6, X7-T7)

Detail information

Logic functions (5-313)

Intended inputs
(Terminal names)

Function

Function name

Dual channel direct opening input

Symbol

Dual Channel

Direct Opening

Description of operation

This function diagnoses the status of
connected safety devices. This function
diagnoses the time interval of status
transition between each input of
duplicated inputs (0.5s).

Safety input 5
(X10-T10, X11-T11)
Safety input 6
(X12-T12, X13-T13)

Detail information

Logic functions (5-311)

Warning

For connected control devices, refer to “SAFETY PRECAUTIONS”.
Safety check signals (pulses signals) are sent from the drive terminals (T0 to T13) to diagnose

connected safety devices and input circuits. Safety check signals can not be used as a power supply
for connected devices.

Note. Solid state outputs, such as safety light curtains, can not be connected.
Note. Use safety inputs as specified combinations, such as receive terminal (Xn) and drive terminal

(Tn). If the combinations are incorrect, SafetyOne does not work correctly.

Note. If there are unused safety inputs, connect the unused receive terminals (Xn) to the

corresponding drive terminals (Tn). If they are not connected, the SafetyOne does not turn ON
the safety outputs.

Advertising