Muting II

This function adds muting to connected safety devices.
As shown in Fig. 5-26, this function is comprised of a safety input (I

n

), a muting input (IM

n

), and a

functional output (O

n

). The output of the muting input function is connected to the muting input

(IM

n

).




Fig. 5-26 Muting II function circuit

Description of operation

The timing is described in Fig. 5-27.

I When the muting input is turned ON while the safety input is ON, the OFF status of the safety

input is suspended, and the output remains ON.

II When the muting input is turned OFF, muting is canceled and the ON/OFF status of the safety

input is shown by the output.

III If muting is not used under the correct conditions, the muting function is disabled and the

ON/OFF status of the safety input is shown by the output.

I

n

IM

n+1

O

n

ON

OFF

Y

m

(Monitor output)

ON

OFF

ON

OFF

ON

OFF

Fig. 5-27 Operation timing of the muting function

Error detection function

Muting monitor
When of the following condition is satisfied, the SafetyOne disables the muting function.
●When the safety device to be muted is OFF

When the muting input is turned ON while the safety input to be muted is OFF, the muting function
is disabled.

Note. lamp outputs (Y17, Y20) have diagnostic functions of wire breaking or no connection of an

indicator in logic 11d. When wire breaking or no connection of an indicator, the SafetyOne
changes to the Stop state and displays "5" in the error LED display.


I

n

IM

n

O

Muting

function

Safety

Input