Wiring example (logic 12c), Logic – IDEC FS1A Controller User Manual

Page 163

Advertising
background image

LOGIC

5-115

Chapter 5

Wiring example (Logic 12C)

In the case where 1 limit switch, 2 safety light curtains, 1 interlock switch, 1 emergency stop switch, and 1
interlock switch with solenoid (spring lock type) are connected.


S1 :Limit

switch

S2, 4

:Safety light curtain

S3 :Interlock

switch

S5

:Emergency stop switch

S6

:Interlock switch with solenoid (spring lock type)

S7 :Start

switch

S8

:Solenoid control switch

(Pressing the solenoid control switches after closing the guard door,
contacts 41-42 and 51-52 of S6 turn on, allowing the SafetyOne to restart.)
K1 to 4 :Contactor
M1, 2

:Motor

V+

X0

X1

X2

X3

T0

T1

T2

T3

24V DC

X5

X6

X7

T5

T6

T7

X10

T10

S5

X4

T4

X11

T11

X12

T12

X13

T13

X14

T14

X15

T15

K1

K2

K3

K4

X16

S7

X17

K1

V-

Y4
Y5
Y6
Y7

Y10
Y11
Y12
Y13
Y14
Y15

Y17

Y20

Y0

Y16

K2

Y1

K3

Y2

K4

Y3

To
PLC

SafetyOne

FE

S3

S1

S2

24V

0V

OSSD1

OSSD2

S4

24V

0V

OSSD1

OSSD2

Guard open

11

12

51

52

42

A1(-)

A2(+

)

41

S6

21

22

S8

Interlock switch with solenoid
(spring lock type)

Actuator

0V DC

Fuse

K2

K1

M1

K4

K3

M2