Safety performance on each wiring of inputs and outputs

Applicable safety performance of SafetyOne depends on wiring of the inputs and outputs.
Wiring examples and achivable safety performances are shown below.

Wiring example of dual channel safety inputs

Dual Channel Safety

X0

X1

T0

T1

24V DC

Safety light curtain

SafetyOne

Control category 4
MTTF

 100 years

DC high
PL e

24V

0V

OSSD1

OSSD2

0V DC

Dual Channel Safety

X0

X1

T0

T1

Emergency stop switch

SafetyOne

Control category 3
MTTF

 100 years

DC Medium
PL d

24V DC

Note:
To avoid short circuit between each cable,
-Fix the cables permanently and protect against external
damage, e.g. by cable ducting, conduit.....
or
-Use individually shielded cables with earth connection.

Dual Channel Safety

X0

X1

T0

T1

Emergency stop switch

SafetyOne

Control category 1
MTTF

 100 years

DC None
PL c

24V DC