●Safety inputs: X0 to X13 (T0, T2 to T5, T12, T13)
Safety inputs are used to diagnose the status of connected safety devices, such as emergency stop
switches, interlock switches, and mode select switches.

Intended inputs
(Terminal names)

Function

Function name

Mode select input

Symbol

Mode Select

Description of operation

This function is for connecting devices
with a mode selector function, such as
mode selector switch. This function
diagnoses time interval of status
transition between each input (0.5s).

Safety input 1
(X0/X1-T0)

Detail information

Logic functions (5-319)

Intended inputs
(Terminal names)

Function

Function name

Dual channel dependent input

Symbol

Dual Channel

D

epende nt

Description of operation

This function diagnoses the status of
connected safety devices. This function
does not diagnose the time interval of
status transition between each input of
duplicated inputs.

Safety input 2
(X2-T2, X3-T3)

Detail information

Logic functions (5-313)

Intended inputs
(Terminal names)

Function

Function name

Dual channel direct opening input

Symbol

Dual Channel

Direct Opening

Description of operation

This function diagnoses the status of
connected safety devices. This function
diagnoses the time interval of status
transition between each input of
duplicated inputs (0.5s).

Safety input 3
(X4-T4, X5-T5)
Safety input 6
(X12-T12, X13-T13)

Detail information

Logic functions (5-311)