IDEC FS1A Controller User Manual

Page 145

Advertising
background image

LOGIC

5-97

Chapter 5

●Start inputs: X16 and X17
Start inputs are used to control the start of safety outputs.

Intended inputs
(Terminal names)

Target safety inputs
(Terminal names)

Function

Function name

Monitor input

Symbol

Single Channel

Monitor

Description of
operation

Safety outputs are started, when
all target safety inputs are in the
safe state and this function is in
the ON state. This function is
turned ON by 0.1s or more ON
operation.

Start input 1
(X16)

Safety input 1
(X0-T0, X1-T1)
Safety input 2
(X2-T2, X3-T3)
Safety input 3
(X4-T4, X5-T5)
Safety input 4
(X6-T6, X7-T7)
Safety input 5
(X10-T10, X11-T11)
Safety input 6
(X12-T12, X13-T13)

Detail information

Logic Functions (5-325)

Intended inputs
(Terminal names)

Target safety
inputs
(Terminal
names)

Function

Function name

Monitor input + Control start

Symbol

Single Channel

Monitor

+

Control

Start

Control

Description of
operation

Safety outputs are started, when this function
becomes ON after all intended safety inputs are
in the safe state. This function is turned ON by
0.1s to 5s ON operation.

Start input 2
(X17)

Safety input 1
(X0-T0, X1-T1)
Safety input 2
(X2-T2, X3-T3)
Safety input 3
(X4-T4, X5-T5)
Safety input 4
(X6-T6, X7-T7)
Safety input 5
(X10-T10,
X11-T11)
Safety input 6
(X12-T12,
X13-T13)

Detail
information

Logic Functions (5-325, 330)

Note. If both of X16 and X17 are turned ON, the SafetyOne will detect an error. As a result, the error

LED displays “3” and the state changes to the Stop state. Use only X16 or X17.

Advertising