IDEC FS1A Controller User Manual

Page 106

Advertising
background image

LOGIC

5-58

●External device monitor inputs: X14 and X15 (T14 and T15)
External device monitor inputs are used to diagnose the status of devices connected to safety outputs.

Intended inputs
(Terminal names)

Target safety
outputs
(Terminal
names)

Function

External device monitor input 1
(X14-T14)

Safety output 1
(Y0, Y1)

Function name

External device monitor input

External device monitor input 2
(X15-T15)

Safety output 2
(Y2, Y3)

Symbol

External Device

Monitor

EDM

Description

of

operation

This function diagnoses the
status of devices connected to a
target safety output.

Detail

information

Logic

functions

(5-326)

Warning

Safety check signals (pulses signals) are sent from the drive terminals (T14, T15) to diagnose external
devices and monitor circuits. Safety checks signal can not be used as a power supply for connected
devices.

Note. If there are unused safety outputs, connect the intended external device monitor terminals (Xn)

to the corresponding drive terminals (Tn). If they are not connected, the SafetyOne detects an
input monitor error. As the result, the error LED displays a “1” and the unit changes to the
Protection state.


Advertising