IDEC FS1A Controller User Manual

Page 240

Advertising
background image

LOGIC

5-192


●State monitor outputs: Y14 to Y16
State monitor outputs are used to output the internal state of SafetyOne.

State

Intended outputs
(Terminal names)

Initial

Run

Configuration

Protection

Stop

State monitor output 1
(Y14)

ON

OFF

OFF

OFF

ON

State monitor output 2
(Y15)

ON

OFF

ON

ON

ON

or□

OFF

State monitor output 3
(Y16)

OFF

ON

OFF

OFF

OFF

Refer to “Chapter 4 BASIC OPERATIONS” and to “Chapter 6 TROUBLE SHOOTING” for details of
each state.

Warning

The monitor outputs are not safety outputs. Do not use these to construct a safety system.


●TEACH monitor outputs: Y17 and Y20
TEACH monitor outputs are used to monitor which of TEACH 1 and TEACH 2 is selected in TEACH
mode.

Intended outputs
(Terminal names)

Target safety inputs
(Terminal names)

Description of operation

TEACH 1 monitor output 1
(Y17)

Safety input 1
(X0-T0: TEACH 1)

When TEACH 1 (X0) is selected, the
monitor output is ON. When TEACH 1 is
not selected, the monitor output is OFF.

TEACH 2 monitor output 2
(Y20)

Safety input 1
(X1-T0: TEACH 2)

When TEACH 2 (X1) is selected, the
monitor output is ON. When TEACH 2 is
not selected, the monitor output is OFF.

Warning

The monitor outputs are not safety output. Do not use these to construct a safety system.

Caution

Refer to "Chapter 2 PRODUCT SPECIFICATIONS" for specifications of each input and output.