IDEC FS1A Controller User Manual

Page 324

Advertising
background image

LOGIC

5-276


●Start inputs: X16 and X17

Start inputs are used to control the start of safety outputs.

Intended inputs
(Terminal names)

Target safety inputs
(Terminal names)

Function

Function name

Monitor input

Symbol

Single Channel

Monitor

Description of
operation

Safety outputs are started,
when all target safety inputs are
in the safe state and this
function is in the ON state. This
function is turned ON by 0.1s or
more ON operation.

Start input 1
(X16)

Safety input 2
(X2, X3)
Safety input 3
(X4, X5)
Safety input 4
(X6, X7)
Safety input 5
(X10, X11)

Detail information

Logic functions (5-325)

Intended inputs
(Terminal names)

Target safety
inputs
(Terminal
names)

Function

Function name

Monitor input + Control start

Symbol

Single Channel

Monitor

+

Control

Start

Control

Description of
operation

Safety outputs are started, when this function
becomes ON after all intended safety inputs
are in the safe state. This function is turned
ON by 0.1s to 5s ON operation.

Start input 2
(X17)

Safety input 1
(X0, X1)

Detail
information

Logic functions (5-325, 330)

Advertising