IDEC FS1A Controller User Manual

Page 4

Advertising
background image

Warning

z

Calculate respective safety distances, taking into consideration the response time of the

SafetyOne, safety devices to be connected to the SafetyOne, and each other device that forms a
part of the system configuration.

z

Applicable safety performance is dependent on each system configuration.

z

Use a power supply that meets following required specifications:

-Conforms to the power supply rating of SafetyOne.
-Complies with the SELV/ PELV circuit specified by EN 50178 or EN60950.
-Has the functionality or the functional equivalent of the control voltage and current of class 2
circuit, as defined in UL508 or UL1310.
-Is in compliance with safety laws and regulations relating to electrical safety, EMC, and like under
the laws and regulations of the country in which it is being used.

z

Ground the V- line (0V DC) for ground diagnosis.

z

In the case of a new configuration or modified installation, be sure to perform a check for each

input and output function.

z

Implement protective measures that personal, other than safety responsible persons operating

the SafetyOne, are unable to modify the configuration.

z

Separate SafetyOne from devices and wires which are not in accordance with class 2 circuit

requirements.


Advertising