LOGIC

5-314

Error detection function

Input monitoring
When an error is detected between dual channel inputs, the SafetyOne changes to the Protection
state and displays "1" on the error LED display. The condition to be detected as an input error is
shown below.
●When there is an independent condition change of 1 of the inputs

The input LEDs blink and the monitoring output (Y

m

) outputs pulses (1 Hz), to notify the operator of

the corresponding input. See Fig. 5-4.


Note. The dependency of the 2 inputs is monitored with the dual channel dependent input function,

but the dependent time is infinite.


Short circuit and grounding detection
When an input error, such as a short circuit or circuit failure, is detected, the SafetyOne changes to
the Stop state and displays "2" on the error LED display.
The input LEDs blink and the monitoring output (Y

m

) outputs pulses (1 Hz), to notify the operator of

the corresponding input.

Noise detection filter
The SafetyOne is tested acording to IEC/EN 61000-6-2, however in the case when the SafetyOne
is used in an environment with severe noise, the SafetyOne changes to the Stop state and displays
"9" on the error LED display.

Warning

Safety check signals (pulses signals) are supplied from the drive circuits (T

n

) to diagnose

connected safety devices and input circuits. Safety check signals can not be used as a power for
connected devices.