Safety output specifications – IDEC FS1A Controller User Manual

Page 21

Advertising
background image

PRODUCT SPECIFICATIONS

2-9

Chapter 2

Safety output specifications

Output type

Source output (N channel MOSFET)

Rated output voltage

Power supply voltage

Minimum voltage

Power supply voltage - 2.0V

Number of output terminals

4 (Y0, Y1, Y2, Y3)

Point

500mA maximum

Maximum output current

total

1A maximum

Leakage current

0.1mA maximum

Allowable inductive Load

Note1

L / R = 25ms

Allowable capacitive load

1uF maximum

Cable length

Note2

100m maximum (total wiring length per 1 output)

Note1. For protection of output circuits, protection devices such as diodes should be connected

to output circuits with inductive loads.

Note2. For cables longer than 30m between SafetyOne and connected devices, use grounded

shielded cables to assure electromagnetic compatibility.


Safety output equivalent circuit

Internal

circuit

Logic

circuit

Y0~Y3

V-

V+

Safety outputs of the SafetyOne are semiconductor outputs. For diagnostics of the shut-off
function, the SafetyOne generates off-pulses in certain intervals when the outputs are in ON
state. The specifications of the safety outputs changes depending on the Logic selected. See
further information in “Chapter 5 LOGIC”. But basic specifications are same.

OFF

ON

OFF interval: approx. 40ms

OFF time: approx. 400μs

Caution

Check the response time of external devices so that they do not correspond to the off pulses.

Monitor and solenoid/lamp outputs do not generate off pulses.

Advertising