LOGIC

5-108

Functions (Logic 12C)


●Safety inputs: X0 to X13 (T0, T1, T4, T5, and T10 to T13)
Safety inputs are used to diagnose the status of connected safety devices, such as emergency stop
switches.

Intended inputs
(Terminal names)

Function

Function name

Dual channel direct opening input

Symbol

Dual Channel

Direct Opening

Description of operation

This function diagnoses the status of
connected safety devices. This function
diagnoses the time interval of status
transition between each input of
duplicated inputs (0.5s).

Safety input 1
(X0-T0, X1-T1)
Safety input 3
(X4-T4, X5-T5)
Safety input 5
(X10-T10, X11-T11)
Safety input 6
(X12-T12, X13-T13)

Detail information

Logic functions (5-311)

Intended inputs
(Terminal names)

Function

Function name

Dual channel safety input

Symbol

Dual Channel Safety

Description of operation

This function diagnoses the status of
connected safety devices. This function
diagnoses the time interval of status
transition between each input of
duplicated inputs (0.1s). The function
does not use drive terminals (T2, T3, T6
and T7).

Safety input 2
(X2, X3)
Safety input 4
(X6, X7)

Detail information

Logic functions (5-317)