Logic – IDEC FS1A Controller User Manual

Page 164

Advertising
background image

LOGIC

5-116

When not using the start switch

Auto start

When not detecting the welding of start switch

Manual start

When detecting the welding of start switch

Control start

When connecting multiple emergency stop switches
in series

NOTE: Safety performance depends on the system
configuration.

When not using some inputs

・If unuse both of S1 and S2, open between the recieve
terminals and drive terminals. This is same for S3 and S4.
(Refer to (1))

If use only S1 of S1 and S2, connect the unused receive

terminals to 24V DC power supply (V+).(Refer to (3))
・If use only S2 of S1 and S2, connect the

unused receive

terminals to corresponded drive terminals. (Refer to (2))

If use only S3 of S3 and S4, connect the unused rceive

terminal to 24V DC power supply (V+).(Refer to (3))

If use only S4 of S3 and S4, connect the unused receive

terminals to corresponded drive terminals. (Refer to (2))
・If there are unsused safety inputs in S5 and S6, connect
the unused recieve terminals to the corresponded drive
terminals. (Refer to (2))

X16
X17

24V DC

X16
X17

24V DC

S7

X10

X11

T10

T11

X12

T12

X13

T13

X

n

X

n+1

T

n

T

n+1

24V DC

(1)

(3)

(2)

X

p

X

p+1

T

p

T

p+1

X

m

X

m+1

T

m

T

m+1

24V DC

X16
X17

S7