LOGIC

5-326

External device monitoring input

This function is for monitoring external devices controlled by the SafetyOne. External devices can
be diagnosed for errors by connecting a NC contact, such as a contactor or a safety relay. As
shown in Fig. 5-17, this function is comprised of an input receiving circuit (X

n

), drive circuit (T

n

), and

functional output.







Fig. 5-17 Circuit for external device monitor input function

Connects to

NC contact on devices such as a contactor, safety relay, or other devices equipped with forced
guided mechanisms

Note. Solid state output devices cannot be connected.

Description of operation

I When a safety check signal from the drive circuit is supplied correctly to the receiving circuit,

the output is turned ON. (Ex. External device is turned OFF.)

II When safety check signal input to the receiving circuit is turned OFF, the output is turned OFF.

(Ex. External device is turned ON.)

III If the safety check signal is not supplied correctly to the receiving circuit due to an error in an

external device or input circuit, the output is turned OFF immediately. Status of the detected
error is displayed on error LED, input LED, and monitor output. (Ex. Fault in external device
or wiring error)

Error detection function

Noise detection filter
The SafetyOne is tested acording to IEC/EN 61000-6-2, however in the case when the SafetyOne
is used in an environment with severe noise, the SafetyOne changes to the Stop state and displays
"9" on the error LED display.

Note. Refer to “Safety output without timer” or to “Safety output with timer” for details of EDM input
monitoring.

X

n

T

n

External device

I

n

External Device

Monitor

EDM