IDEC FS1A Controller User Manual

Page 228

Advertising
background image

LOGIC

5-180

When using the start switch S7

Manual start

When not using the start switch S7

Auto start

When connecting multiple emergency stop switches
in series

NOTE: Safety performance depends on the system
configuration.

When not using some safety inputs

If there are unused safety inputs in S3 to S5,

connect the unused receive terminals to the
corresponding drive terminals. (Refer to (1))

If S6 is not used, connect the receive terminal to

24V DC power supply (V+). (Refer to (2))

X16
X17

24V DC

S8

X16
X17

24V DC

S7

S8

X4

X5

T4

T5

X10

T10

X11

T11

X

n

X

n+1

T

n

T

n+1

24V DC

X

m

X

m+1

T

m

T

m

(1)

(2)



Advertising