LOGIC

5-203

Chapter 5


●Safety outputs: Y0 to Y3

Safety outputs are used to output safety information processed by SafetyOne.

Intended outputs
(Terminal names)

Function

Function name

Safety output without timer

Symbol

Hold

EDM

OSSD

Description of operation

This function is a safety output to output safety
information processed by SafetyOne. The
output is turned OFF immediately by OFF
operation (instantaneous OFF output).

Safety output 1-1
(Y0)
Safety output 2
(Y2)
Safety output 3
(Y3)

Detail information

Logic functions (5-332)

Intended outputs
(Terminal names)

Function

Function name

Safety output with timer

Symbol

Hold

EDM

OSSD

with

Off delay

Description of operation

This function is a safety output to output safety
information processed by SafetyOne. The
output is turned OFF after the preset time of the
OFF-delay timer (OFF-delay output).

Safety output 1-2
(Y1)

Detail information

Logic functions (5-335)

Note. When the SafetyOne changes to Protection state due to input monitor error, safety output

without timer (safety output 1-1, safety output 2, and safety output 3) is turned OFF. Safety
output with timer (safety output 1-2) is turned OFF after the preset OFF-delay time.

Note. When the SafetyOne changes to Stop state due to circuit failure or other errors, all safety

outputs (safety output 1-1, safety output 1-2, safety output 2, and safety output 3) are turned
OFF, immediately.

Note. Set time of safety output with timer is active independent of the selected mode.