IDEC FS1A Controller User Manual

Page 135

Advertising
background image

LOGIC

5-87

Chapter 5


●State monitor outputs: Y14 to Y16
State monitor outputs are used to output the internal state of SafetyOne.

State

Intended outputs
(Terminal names)

Initial

Run

Configuration

Protection

Stop

State monitor output 1
(Y14)

ON

OFF

OFF

OFF

ON

State monitor output 2
(Y15)

ON

OFF

ON

ON

ON

or □

OFF

State monitor output 3
(Y16)

OFF

ON

OFF

OFF

OFF

Refer to “Chapter 4 BASIC OPERATIONS” and to “Chapter 6 TROUBLE SHOOTING” for details of
each state.

Warning

The monitor outputs are not safety outputs. Do not use these to construct a safety system.


●Solenoid output: Y17
Solenoid output is used to control a solenoid in an interlock switch.

Intended outputs
(Terminal names)

Description of operation

Solenoid output 1
(Y17)

When safety output 1 is OFF, the solenoid output is ON. When safety
Output 1 is ready to turn ON (safety output 1 can be turned ON by
operation of the start input), the solenoid output is OFF.

Warning

The solenoid output is not safety output. Do not use these to construct a safety system.

Note. The solenoid output is OFF in each state except Run state.

Caution

Refer to "Chapter 2 PRODUCT SPECIFICATIONS" for specifications of each input and output.