Functions (logic 12a) – IDEC FS1A Controller User Manual

Page 130

Advertising
background image

LOGIC

5-82

Functions (Logic 12A)


●Safety inputs: X0 to X13 (T4 to T13)

Safety inputs are used to diagnose the status of connected safety devices, such as emergency stop
switches, and input devices for two-hand control.

Intended inputs
(Terminal names)

Function

Function name

Dual channel safety input

Symbol

Dual Channel Safety

Description of operation

This function diagnoses the status of
connected safety devices. This function
diagnoses the time interval of status
transition between each input of
duplicated inputs (0.1s). The function
does not use drive terminals (T0 to T3).

Safety input 1
(X0, X1)
Safety input 2
(X2, X3)

Detail information

Logic functions (5-317)

Intended inputs
(Terminal names)

Function

Function name

Dual channel direct opening input

Symbol

Dual Channel

Direct Opening

Description of operation

This function diagnoses the status of
connected safety devices. This function
diagnoses the time interval of status
transition between each input of
duplicated inputs (0.5s).

Safety input 3
(X4-T4, X5-T5)
Safety input 4
(X6-T6, X7-T7)

Detail information

Logic functions (5-311)

Intended inputs
(Terminal names)

Function

Function name

Dual channel NO/NC input

Symbol

Dual

Channel

NO /NC

Description of operation

This function diagnoses the status of
connected safety devices. This function
diagnoses the time interval of status
transition between each input of
duplicated inputs (0.5s).

Safety input 5
(X10-T10, X11-T11)
Safety input 6
(X12-T12, X13-T13)

Detail information

Logic functions (5-315)