LOGIC

5-62


●Muting lamp outputs: Y17 and Y20
Muting lamp outputs are used to control muting lamps.

Intended outputs
(Terminal names)

Target safety inputs
(Terminal names)

Description of operation

Muting lamp output 1
(Y17)

Safety input 1
(X0, X1)

The output is ON, during safety input 1 is muting state by
muting input 1.

Muting lamp output 2
(Y20)

Safety input 2
(X4, X5)

The output is ON, during safety input 2 is muting state by
muting input 2.

Warning

The muting lamp outputs are not safety outputs. Do not use these to construct a safety system.

Note. Muting lamp output terminals (Y17 and Y20) detect that muting lamps are disconnected or

unconnected. If these failures are detected, the error LED displays “5” and the state changes to
the Stop state.

Note. If there is an unused muting lamp output, connect a resistor (10 kΩ, 1/4W) to the unused

terminals.

Caution

Refer to "Chapter 2 PRODUCT SPECIFICATIONS" for specifications of each input and output.