Warning

z

Do not connect devices having input and output specifications that do not satisfy the

requirements of the SafetyOne.
Refer to the following for information on the requirements of connected devices.

Connected Control Device

Requirements

Emergency stop switch

Device equipped with a direct opening action mechanism conforming to

IEC/EN60947-5-5 or indicated in IEC/EN60947-5-1

Interlock switch,
limit switch

Device equipped with a direct opening action mechanism indicated in

IEC/EN60947-5-1

Interlock switch with lock

Spring lock interlock switch with solenoid

Mode select switch

Device conforming to regulations of the country where used and required

categories (for example, switch conforming to IEC/EN60947-1)

Enabling switch

Device conforming to IEC/EN60947-5-8 (or IEC/EN60947-5-1)

Solid state output device

Device conforming to regulations of the country where used (for example,

safety light curtain conforming to IEC/EN61496-1)
PNP output (See Note 1)

Non-contact interlock switch IDEC HS7A series
Safety relay

Relay equipped with forced guide mechanism or conforming to EN50205

Contactor
(electromagnetic switch)

Contactor equipped with forced guide mechanism

Other control devices

Use start switches and other devices that conform to the regulations of the

country where used.

Muting sensor

Device conforming to IEC/EN60947-5-2 as shown below
-3 wire transmission (dark on) photoelectric switch which has a PNP open

collector output.
-3 wire (normal open) proximity switch which has a PNP open collector

output.

Muting lamp

Incandescent bulb indicator light conforming to IEC/EN60947-1 or

IEC/EN60947-5-1
Note 2: It is not possible to detect a disconnection of the muting lamp when

using an LED indicator light.

Input device for two-hand

control

Device witch the structure conforming to ISO13851, and consists of

momentary switches conforming to IEC/EN 60947-5-1 with NO/NC contacts.


z

Make sure that the end-user thoroughly understands the contents of this user’s manual.

Note 1. SafetyOne reads input data at regular intervals. Use a solid state output device that sends

output signals of the waveforms shown below. Otherwise the SafetyOne cannot process the input
signal correctly.

Applicable solid state
output device

Pulse output off cycle of 40ms or
more and an off time of 1ms or less.

Pulse output off time of 0.5ms or
less.

(Waveform of solid sate
output)

The device may not be usable even if the above specifications are satisfied. Be sure to
thoroughly confirm operations using the actual device.

Off cycle: 40ms or more

Off time:
1ms or less

Off time: 0.5ms or less