Logic, Example: teach 2 – IDEC FS1A Controller User Manual

Page 244

Advertising
background image

LOGIC

5-196

Example: TEACH 2

Monitor output for
Safety output 1: Y12

State monitor output 3:
Y16

Safety input 1: X0
(Mode select input:
Teach 1)

Safety input 2: X2
(Mode select input:
Teach mode)

Monitor output for
safety input 2: Y5

Monitor output for
safety input 1: Y4

Monitor output for
safety input 3: Y6

Safety input 1: X1
(Mode select input:
Teach 2)

Safety input 3:
X4, X5

Start input 2: X17
(Control)

Safety input 2: X3
(Mode select input:
Auto mode)

Max. 0.1s

Safety output 1: Y0,
Y1

Safety output 2: Y2,
Y3

Monitor output for
Safety output 2: Y13

Monitor output for
Teach 1: Y17

Start input 1: X16
(Manual)

Min. 0.1s

Safety input 4:
X6, X7

Monitor output for
safety input 6: Y11

Safety input 6: X12,
X13

Max. 0.1s

0.1s to 5s

Monitor output for
Teach 2: Y20

Monitor output for
safety input 4: Y7

Safety input 5: X10,
X11

Monitor output for
safety input 5: Y10

note 1)

OFF delay time

OFF delay time

OFF delay time

Safety

output

ON

Safety

output

ON

Safety

output

ON

Switch to

Auto mode

Max. 3s

Note 1) When “Safety input 2 (mode select input)” is switched to Auto mode from Teach mode, all of “Safety output”

are kept ON for 3s maximum till X3 is turned ON after X2 is turned OFF.
All of “Safety output” are turned OFF at the same time as X3 is turned ON.