Start input specifications, Warning – IDEC FS1A Controller User Manual

Page 20

Advertising
background image

PRODUCT SPECIFICATIONS

2-8

Start input specifications

Rated input voltage

24V DC

Input ON voltage

15.0V DC to 28.8V DC

Input OFF voltage

Open or 0V DC to 5.0V DC

Number of start input terminals

2 (X16,17)

Input current

5mA per port (at rated voltage)

Type of input

Sink type input (for PNP output), Type 1 (IEC/EN61131-2)

Cable length

Note1

100m maximum (total wiring length per 1 input)

Allowable wiring resistance

300Ω maximum

Note1. For cables longer than 30m between SafetyOne and connected devices, use grounded

shielded cables to assure electromagnetic compatibility.


Start input equivalent circuit







Start input operating range












The specifications of the start inputs changes depending on the Logic selected. See further
information in “Chapter 5 LOGIC”. But basic specifications are same.

Warning

Do not use start inputs as safety inputs. This may cause the loss of safety functions and
possible failure in the SafetyOne or peripherals.

Voltage(V)

Current

(mA)

28.8

24

15

5

0.5 3

5

6

ON area

Transition area

OFF area


In
te
rn
a

l C
ir

c

ui
t

4.7kΩ

V-

X16, X17

Advertising