Timing chart (logic 11d), Logic, Example: manual start input (x16) is used – IDEC FS1A Controller User Manual

Page 113

Advertising
background image

LOGIC

5-65

Chapter 5

Timing chart (Logic 11d)

Example: Manual start input (X16) is used.

Safety input 1:
X0, X1

Start input 1: X16
(Manual)

Safety output 1:
Y0, Y1

Monitor output for
safety input 1: Y4

Monitor output for
Safety output 2: Y13

Muting lamp output 1:
Y17

Muting input 1: X2

State monitor output 3:
Y16

note 1)

Muting

start

Muting

end

Muting

end

Min. 0.1s

Max. 6s

Initialization

Max. 0.1s

Muting input 1: X3

note 1)

note 3)

note 3)

Monitor output for
Safety output 1: Y12

Safety output 2:
Y2, Y3

note 2)

Power

ON

Safety

output

ON

Safety
output

ON

Muting

start

OFF delay time

(Safety input 2, 3 and 4 are all ON and muting input 2 is OFF in this chart.)


Note 1) When “Safety input 1” is turned OFF before “Muting input 1” is turned ON, muting function is not effective and

all of “Safety output” are not turned ON. “Safety input 2” and “Muting input 2” is as well.

Note 2) When “Muting input 1” is turned ON while “Safety input 1” is ON, muting function is effective.

In fact all of “Safety output” are turned ON when “Start input” is turned ON. It does not depend on a condition
of “Safety input 1” among muting function is effective. “Safety input 2” and “Muting input 2” is as well.

Note 3) Input monitor error detection time is 3s.

About safety inputs that are not described in this chart, input monitor error detection time is as follows.

The time of dual channel safety input (X0, X1, X4, and X5) is 0.1s.

The time of muting input (X6, X7) is 3s.

The time of dual channel direct opening input (X10 to X13) is 0.5s.

Refer to the following “Logic functions” for more details.