Error detection function – IDEC FS1A Controller User Manual

Page 372

Advertising
background image

LOGIC

5-324

X

n

X

n+1

I

n

ON

OFF

Input monitor error
detection time:Max.3s

Independent conditon
change in one input

Y

m

(Monitor output)

SafetyOne changes to
Protection State after an input
monitor error is detected.

1Hz pulse signal is output from
corresponded monitor output.

0.5s

0.5s

ON

OFF

ON

OFF

ON

OFF

Cance-

llation

Fig. 5-14 Operation timing of the muting input function

Error detection function

Input monitoring and grounding detection
When an error is detected at the inputs, the SafetyOne changes to the Protection state and
displays "1" on the error LED display. The conditions to be detected as an input error are shown
below.

●When the input monitor error detection time (3s) is exceeded during the 2 input conditions and

they do not match (namely ON/OFF or OFF/ON).

●When there is an independent condition change of the 1 of the input.
●When the ON state of the input goes to the ground state.

The input LEDs blink and the monitoring output (Y

m

) send pulses (1Hz), to notify the operator of the

corresponding input. See Fig. 5-14

Noise detection filter
The SafetyOne is tested acording to IEC/EN 61000-6-2, however in the case when the SafetyOne
is used in an environment with severe noise, the SafetyOne changes to the Stop state and displays
"9" on the error LED display.

Note. Drive circuit corresponding to muting input (T

n

, T

n+1

) is always OFF.