Timing chart (logic 12a), Logic, Example: manual start input (x16) is used – IDEC FS1A Controller User Manual

Page 138

Advertising
background image

LOGIC

5-90

Timing chart (Logic 12A)

Example: Manual start input (X16) is used.

Min. 0.1s

Safety input 1: X0,
X1

Start input 1: X16
(Manual)

Safety output 1:
Y0, Y1

Monitor output for
safety input 1: Y4

Monitor output for
Safety output 1: Y12

State monitor output 3:
Y16

Monitor output for
two-hand control
function: Y20

OFF delay time

Max. 6s

Initialization

Safety input 5: X10

Monitor output for
safety input 5: Y10

Safety input 5: X11

note 1)

note 1)

Safety output 2:
Y2, Y3

Monitor output for
Safety output 2: Y13

Solenoid output 1:
Y17

Safety input 6: X13

Monitor output for
safety input 6: Y11

Safety input 6: X12

Power

ON

Safety

output

1

ON

note 2)

Safety
output

2

ON

Safety
output

1

ON

Safety

output

2

ON

OFF delay time

Max. 0.1s

(Safety input 2, 3 and 4 are all ON in this chart.)


Note 1) Input monitor error detection time is 0.5s.
Note 2) “Safety output 2” is not turned ON when time lag between “Safety input 5” and “Safety input 6” for two-hand

control function is more than 0.5s. Refer to the following “Logic function” for more details.


About safety inputs that are not described in this chart, input monitor error detection time is as follows.

The time of dual channel safety input (X0 to X3) is 0.1s.

The time of dual channel direct opening input (X4 to X7) is 0.5s.

The time of dual channel NO/NC input (X10 to X13) is 0.5s.

Refer to the following “Logic functions” for more details.