LOGIC

5-33

Chapter 5

Unused safety inputs

Terminal names

Connection

X0-T0 Open

Safety input 1

X1-T1 Short
X2-T2 Open

Safety input 2

X3-T3 Short
X4-T4 Open

Safety input 3

X5-T5 Short
X6-T6 Open

Safety input 4

X7-T7 Short
X10-T10 Short

Safety input 5

X11-T11 Short
X12-T12 Short

Safety input 6

X13-T13 Short


●External device monitor inputs: X14 and X15 (T14 and T15)
External device monitor inputs are used to diagnose the status of devices connected to safety outputs.

Intended inputs
(Terminal names)

Target safety
outputs
(Terminal
names)

Function

External device monitor input 1
(X14-T14)

Safety output 1
(Y0, Y1)

Function name

External device monitor input

External device monitor input 2
(X15-T15)

Safety output 2
(Y2, Y3)

Symbol

External Device

Monitor

EDM

Description

of

operation

This function diagnoses the
status of devices connected to a
target safety output.

Detail

information

Logic

functions

(5-326)

Warning

Safety check signals (pulses signals) are sent from the drive terminals (T14, T15) to diagnose external
devices and monitor circuits. Safety check signals can not be used as a power supply for connected
devices.

Note. If there are unused safety outputs, connect the intended external device monitor terminals (Xn)

to the corresponding drive terminals (Tn). If they are not connected, the SafetyOne detects an
input monitor error. As the result, the error LED displays a “1” and the unit changes to the
Protection state.