Alarm connectors, Network standards, Management – Carrier Access Network Device Axxius 800 User Manual

Page 40: Power, Physical information, Environment

Advertising
background image

1-8

Axxius 800 - Release 2.2

Base Platform

Technical Specifications

Alarm Connectors

The alarm contact outputs are per Telcordia definitions for visible and audible. They
operate per the spec with the exception that the audible outputs can be disabled with the
ACO button.

l

The alarm output contacts are designed for use at 48V nominal with a current
draw of 0.5A maximum.

l

The alarm inputs are dry contact with a current capacity of 10mA.

Network Standards

l

ANSI/TIA - T1.403 ESF FDL

Management

l

Craft Interface - front access from RS-232 (DB9) or 10/100Base-TX Ethernet
ports

l

SNMP

l

Dedicated Management DS0 for remote management access

Power

l

DC Power: -48 VDC or +24 VDC, 120 W rated input

l

OCU-DP and FXO Service cards require -48 VDC Power Supply

l

Dual-feed power inputs located on rear panel

Physical Information

l

Dimensions: 3.5 in. (H-2 RU) x 17.25 in. (W) x 12.5 in. (D)
8.9 cm (H) x 43.8 cm (W) x 31.75 cm (D)

l

Weight: approximately 30 lbs. (13.6 kg) fully loaded

l

Rack mount, 19 or 23 inch

Environment

See Installation Environment on page 2-3