Chassis ground connector, Chassis ground connector -6 – Carrier Access Network Device Axxius 800 User Manual

Page 62

Advertising
background image

3-6

Axxius 800 - Release 2.2

Electrical Installation and Cabling

Chassis Connections

Chassis Ground Connector

1. Route wire (#6 or #8 AWG copper) from building ground to lug on Axxius 800.

2. Strip insulation off wire end, if necessary.

3. Loosen compression screw until opening is large enough to accept ground wire.

4. Insert ground wire into lug barrel, beneath compression plate and tighten

compression screw.

5. Attach ground lug to chassis

Ground Terminals

Ground Lug

Compression
Screw

Lug Barrel

Advertising