IAI America XSEL-KE User Manual

Page 69

Advertising
background image

54

Part 2 Operation

INTELLIGENT ACTUATOR

(2) Timing

chart

[1] Program

start

Program number

input

Program 1 Program 2

External start

input

T1: Duration after the ready output turns ON until input of

external start signal is permitted
T1 = 10 msec min.

T2: Duration after the program number is input until input

of external start signal is permitted
T2 = 50 msec min.

T3: Input duration of external start signal

T3 = 100 msec min.

[2] Auto program start

 :KHQ,2SDUDPHWHU1RLVVHWWR³´ 

Input of input

function 003

Ready output

Ready output

Auto program

start

[3] Software reset signal

 :KHQ,2SDUDPHWHU1RLVVHWWR³´ 

Input of input

function 001

Ready output

Program

starting

[4] Servo ON signal

 :KHQ,2SDUDPHWHU1RLVVHWWR³´ 

Input of input

function 002

Ready output

Servo ON

[5] When the recovery type after emergency stop or enabling

RSHUDWLRQLVVHWWR³2SHUDWLRQFRQWLQXHG´
 :KHQ,2SDUDPHWHU1RLVVHWWR³´

6HW,2SDUDPHWHU1RWR³´ RSHUDWLRQSDXVHUHVHWVLJQDO  
6HW,2SDUDPHWHU1RWR³´ GULYHVRXUFHFXWRIIUHVHWLQSXW  

Program

starting

Emergency

stop

'ULYHVRXUFH

cutoff reset

Pause reset

T1: Time after the ready output turns ON until input

function 003 can be input
T1 = 10 msec min.

* Auto program start:

Set the program you want to start automatically in
2WKHUSDUDPHWHU1R³$XWRVWDUWSURJUDPQXPEHU´

T1: Time after the ready output turns ON until input

function 001 can be input
T1 = 10 msec min.

T2: Time until the software reset signal functions

T2 = 1 sec .

T3: Time after the software reset signal is reset until the

ready signal is output

T1: Time after the ready output turns ON until input

function 002 can be input
T1 = 10 msec min.

T2: Interval after the servo turns OFF until it turns ON

again
T2 = 1.5 sec min.

T1:

Time after the emergency stop input is reset until the
GULYHVRXUFHFXWRIIUHVHWVLJQDOFDQEHLQSXW

T1 = 2 msec min.

T2:

7LPHGXULQJZKLFKWKHGULYHVRXUFHFXWRIIUHVHW
signal is input

T1 = 10 sec min.

T3: Time during which the pause reset signal is input

T1 = 10 sec min.