6. Operating, maintenance and diagnosis

6-10

Festo P.BE-MTR-DCI-IO-EN en 1209d

Fault

Possible cause

HARDWARE ERROR

Device fault e.g. EEPROM defective.

Please contact your Festo Service.

HOMING ERROR

Fault during homing run
Possible causes:
– homing run interrupted
– Reference switch defective

If necessary, check the function of the reference switch

It is essential that you repeat the homing run.

i

2

t-ERROR

Current monitoring i

2

t.

Possible cause
The drive is blocked.

Check the mechanical parts of the drive.

LAST ACTUAL
POSITION NOT SAVED
PLEASE ENFORCE
HOMING RUN

When starting a positioning set:
Possible causes:
Valid homing run has not yet been carried out.

You must carry out homing run.

The following applies up to firmware version V1.35: If the CI-parameter
60FBh, subindex 20h, does not contain the value 240 (0x00F0), over-
write this with value 240 (0x00F0), see appendix B.1.4.

MOTOR STOP

Fault during the positioning procedure
Possible cause
The positioning procedure is discontinued on the control panel with
EMERG.STOP (<Menu> button).

Quit the fault on the control panel with <Enter>

OVERHEATING

Overheating (operating temperature > 80 °C)
Possible cause
– Motor overloaded
– Ambient temperature too high

Check ...
– that the limits are observed (motor characteristic curves)
– the mechanical parts e.g. for stiffness.

If necessary, reduce the ambient temperature.