B. Supplementary information

B-28

Festo P.BE-MTR-DCI-IO-EN en 1209d

Position_Window_Time

CI access

6068h

00h

Var

uint16

rw*

Description

Readjustment time in milliseconds.
Once the actual position has been in the target position window for this amount
of time, the ”Target reached” bit will be set in the status word (object 6041).
Range of values: 1...30000
Default:
MTR-DCI-32/42...:

100 ms

MTR-DCI-52...:

100 ms

MTR-DCI-62...:

400 ms

* Write only Festo (factory or service)

Velocity_Target_Value

CI access

606Bh

00h

Var

int32

r

Description

Current nominal speed value of speed regulator in increments.
Value range: -2

31

...+(2

31

-1)

Velocity_Actual_Value

CI access

606Ch

00h

Var

int32

r

Description

Current nominal speed value of speed regulator in increments.
Value range: -2

31

...+(2

31

-1)

Max_Current

CI access

6073h

00h

Var

uint16

rw

Description

Maximum motor current in 1/1000 of the specified rated current Identical to
Object 6510/41. No adaption is necessary for positioning axis DMES-...
In homing mode: Nominal value for the current regulator. Limits the motor force
during homing run towards the stop and, in the event of a fault, protects the
stops during homing run to a reference switch.
Note that the current limitation also limits the maximum possible speed and
the nominal set speeds may not, therefore, be achieved or (e.g. in vertical oper-
ation) homing run is not carried out.
Value range: 1...2000 (0x0001...0x07D0)
Default: 1500 (0x05DC) = rated motor current x 1.5