5. Commissioning

5-13

Festo P.BE-MTR-DCI-IO-EN en 1209d

Discontinue homing run

If necessary, homing run can be discontinued with the <Menu>
button (EMERG STOP). If homing run is interrupted, the dis-
play will show the fault message HOMING ERROR. If a correct
homing run has already been carried out, the previous refer-
ence point will retain its validity.

Quit the fault message with <Enter>.

Repeat homing run.

Fault during homing run

If a fault occurs during homing run:

quit the fault message with <Enter>

if necessary, check the function of the reference switch

check the settings of the parameters.

If necessary, position the drive in Teach mode so that at
the start it stands in the search direction

in front of the

stop or reference switch.

Repeat homing run.

5.2.3

Teach the axis zero point and the software end positions

Prerequisites for teaching the axis zero point and the
software end positions:

Homing run was successful.

Note
When homing run to a stop, set the offset of the axis zero
point to ≠ 0. You will then prevent movement to the mech-
anical end positions during operation.