B. Supplementary information

B-25

Festo P.BE-MTR-DCI-IO-EN en 1209d

Group 6xxx

Note
The control parameters (6068h, 60FBh) of the MTR-DCI are
pre-set. Modification is only permitted for service purpo-
ses. If necessary consult Festo.

Control_Word

CI access

6040h

00h

Var

uint16

w

Description

Modify the current regulator status or trigger an activity.
As status modifications require a certain amount of time, all status modifica-
tions triggered via the Control Word must be read back via the Status Word
(Object 6041). Only when the requested status can be read in the Status Word,
may a further command be written via the Control Word.
Typical values see Tab. B/1.

Value

Mask

Function

0x000F

ENABLE OPERATION Controller enable

0x000D

0x000D

VOLTAGE DISABLED end stage OFF

0x001F

Start ABSOLUTE movement

0x005F

Start RELATIVE movement

0x010F

0x0100

Stop movement

0x008F

0x0080

Reset fault + ENABLE OPERATION
Reply without 0x0080 – mask

0x004F

0x0040

Set target position as RELATIVE

Tab. B/1:

Typical values of the control word