B. Supplementary information

B-25

Festo P.BE-MTR-DCI-IO-EN en 1209d

Group 6xxx

Note
The control parameters (6068h, 60FBh) of the MTR-DCI are
pre-set. Modification is only permitted for service purpo-
ses. If necessary consult Festo.

Control_Word

CI access

6040h

00h

Var

uint16

w

Description

Modify the current regulator status or trigger an activity.
As status modifications require a certain amount of time, all status modifica-
tions triggered via the Control Word must be read back via the Status Word
(Object 6041). Only when the requested status can be read in the Status Word,
may a further command be written via the Control Word.
Typical values see Tab. B/1.

Value

Mask

Function

0x000F

–

ENABLE OPERATION Controller enable

0x000D

0x000D

VOLTAGE DISABLED end stage OFF

0x001F

–

Start ABSOLUTE movement

0x005F

–

Start RELATIVE movement

0x010F

0x0100

Stop movement

0x008F

0x0080

Reset fault + ENABLE OPERATION
Reply without 0x0080 – mask

0x004F

0x0040

Set target position as RELATIVE

Tab. B/1:

Typical values of the control word