Group 6xxx – Festo Электромотор MTR-DCI User Manual
Page 161
![background image](/manuals/464459/161/background.png)
B. Supplementary information
B-25
Festo P.BE-MTR-DCI-IO-EN en 1209d
Group 6xxx
Note
The control parameters (6068h, 60FBh) of the MTR-DCI are
pre-set. Modification is only permitted for service purpo-
ses. If necessary consult Festo.
Control_Word
CI access
6040h
00h
Var
uint16
w
Description
Modify the current regulator status or trigger an activity.
As status modifications require a certain amount of time, all status modifica-
tions triggered via the Control Word must be read back via the Status Word
(Object 6041). Only when the requested status can be read in the Status Word,
may a further command be written via the Control Word.
Typical values see Tab. B/1.
Value
Mask
Function
0x000F
–
ENABLE OPERATION Controller enable
0x000D
0x000D
VOLTAGE DISABLED end stage OFF
0x001F
–
Start ABSOLUTE movement
0x005F
–
Start RELATIVE movement
0x010F
0x0100
Stop movement
0x008F
0x0080
Reset fault + ENABLE OPERATION
Reply without 0x0080 – mask
0x004F
0x0040
Set target position as RELATIVE
Tab. B/1:
Typical values of the control word