6 connecting the higher-order controller – Festo Электромотор MTR-DCI User Manual

Page 56

Advertising
background image

3. Installation

3-14

Festo P.BE-MTR-DCI-IO-EN en 1209d

3.6

Connecting the higher-order controller

Communication with the higher-order controller is made via
the control connection on the MTR-DCI

Use the control cable KES-MC-1-SUB-9 to connect the
MTR-DCI to a higher-level controller (PLC).

Caution
Long I/O signal cables reduce the immunity to interfer-
ence.

Do not, therefore, exceed the maximum permitted I/O
signal cable length of 30 m.

Sub-D plug

Colour

1)

Description

1

9

1

white

I1

Position set code Bit0

2

brown

I2

Position set code Bit1

3

green

I3

Position set code Bit2

4

yellow

I4

Position set code Bit3

5

grey

I5

START

6

pink

I6

ENABLE

7

blue

O1

READY

8

red

O2

MOTION COMPLETE (MC)

9

black

GND

GROUND (basis potential)

1)

Cable colours of pilot line KES-MC-1-SUB-9

Tab. 3/8:

“Controller” connection on the MTR-DCI