Setting 6: preset 6 – Yaskawa J1000 Compact Vector Control Drive User Manual

Page 100

Advertising
background image

No.

Parameter Name

Default Setting

E1-03

V/f Pattern Selection

0FH

L2-01

Momentary Power Loss Operation Selection 1: Enabled

L3-04

Stall Prevention Selection during

Deceleration

1: Enabled

Table 4.12 Compressor: User Parameters (A2-01 to A2-16):

No.

Parameter Name

No.

Parameter Name

b1-01

Frequency Reference Selection 1

E1-03 V/f Pattern Selection

b1-02

Run Command Selection 1

E1-07 Middle Output Frequency

b1-04

Reverse Operation Selection

E1-08 Middle Output Frequency Voltage

C1-01 Acceleration Time 1

E2-01 Motor Rated Current

C1-02 Deceleration Time 1

u

Setting 6: Preset 6

Note:

1. Read the instructions listed in Notes on Controlling the Brake when Using Application Preset 6 on

page

101

when using Application Preset 6

2. Perform Auto-Tuning after selecting Application Preset 6.
3. If UL3 appears on the operator display after Auto-Tuning is complete, set L6-01 to “0” to repeat the

Auto-Tuning process.

Table 4.13 Preset 6: Parameters and Settings

No.

Parameter Name

Default Setting

A1-02

Control Method Selection

2: Open Loop Vector Control

b1-01

Frequency Reference Selection 1

0: Operator

b6-01

Dwell Reference at Start

3.0 Hz

b6-02

Dwell Time at Start

0.3 s

C1-01

Acceleration Time 1

3.0 s

C1-02

Deceleration Time 1

3.0 s

C6-01

Drive Duty Selection

0: Heavy Duty

C6-02

Carrier Frequency Selection

2: 5 kHz

d1-01

Frequency Reference 1

6.0 Hz

d1-02

Frequency Reference 2

30.0 Hz

d1-03

Frequency Reference 3

60.0 Hz

E1-03

V/f Pattern Selection

0FH

H2-02

Terminals P1 Function Selection

37: During Frequency Output

4.5 Application Selection

100

YASKAWA ELECTRIC TOEP C710606 47C YASKAWA AC Drive – V1000 Quick Start Guide