Name

Description

d1-13

Frequency Reference 13

Frequency reference when digital inputs “Multi-Step Speed

Reference 3, 4” (H1- = 5 and 32) are on.

d1-14

Frequency Reference 14

Frequency reference when digital inputs “Multi-Step Speed

Reference 1, 3, 4” (H1- = 3, 5, 32) are on.

d1-15

Frequency Reference 15

Frequency reference when digital inputs “Multi-Step Speed

Reference 2, 3, 4” (H1- = 4, 5, 32) are on.

d1-16

Frequency Reference 16

Frequency reference when digital inputs “Multi-Step Speed

Reference 1, 2, 3, 4” (H1- = 3, 4, 5, 32) are on.

d1-17

Jog Frequency Reference

Frequency reference when digital inputs “Jog Frequency Reference,”

“Forward Jog” or “Reverse Jog.” are on.

d2: Frequency Upper and Lower Limits

Use d2 parameters to configure the frequency reference limits.

d2-01

Frequency Reference Upper Limit

Sets the frequency reference upper limit as a percentage of maximum

output frequency (E1-04).

d2-02

Frequency Reference Lower Limit

Sets the frequency reference lower limit as a percentage of maximum

output frequency (E1-04).

d2-03

Master Speed Reference Lower

Limit

Refer to V1000 Technical Manual for details.

d3: Jump Frequency

Use d3 parameters to configure the drive Jump Frequency settings.

d3-01

Jump Frequency 1

d3-01 to d3-04 allow programming of three prohibited frequency

reference points for eliminating problems with resonant vibration of

the motor / machine.

d3-02

Jump Frequency 2

d3-03

Jump Frequency 3

d3-04

Jump Frequency Width

This parameter sets the dead-band width around each selected

prohibited frequency reference point.

d4: Frequency Reference Hold

Use d4 parameters to configure the drive frequency reference hold function.

d4-01

Frequency Reference Hold Function

Selection

0: Disabled

1: Enabled

d4-03

Frequency Reference Bias Step (Up/

Down 2)

Sets the bias added to the frequency reference when the Up/Down 2

digital inputs are set.

d4-04

Frequency Reference Accel/Decel

(Up/Down 2)

0: Adjusts bias value according to currently selected accel/decel time.

1: Adjusts the bias value by Accel/Decel Time 4 (C1-07 and C1-08).

d4-05

Frequency Reference Bias Operation

Mode Selection (Up/Down 2)

0: Holds the bias value when Up/Down 2 reference is on or off.

1: When the Up 2 reference and Down 2 reference are both on or both

off, applied bias becomes 0 using currently selected accel/ decel.

times.

d4-06

Frequency Reference Bias (Up/

Down 2)

Saves the bias value once the frequency reference is adjusted.

d4-07

Analog Frequency Reference

Fluctuation Limit (Up/Down 2)

When the Up 2 and Down 2 commands are enabled, the frequency

reference holds the bias value as the levels for the analog frequency

reference or pulse train frequency reference change, accelerating or

decelerating to the frequency reference.

B.1 Parameter Table