Basic Drive Setup Adjustments

This section explains the basic settings required for initial drive operation. Checking these

basic parameter settings during start-up will help to ensure a successful drive start-up.
If more information is required for parameters not listed in this section,

Refer to Parameter

List on page 175

as required for a complete listing of drive parameters.

u

Control Mode Selection: A1-02

Note:

1. Be sure to perform Auto-Tuning when using one of the vector control modes.
2. Reinitializing the drive does not reset A1-02 to the factory default value.

n

Available Control Modes

Three motor control modes are available. Select the control mode that best suits the application

in which the drive will be used.

Control Mode

Parameter

Main Applications

V/f Control

A1-02 = 0

(default)

• General variable speed applications
• For running multiple motors from a single drive
• When replacing a drive in which parameter settings are

unknown.

Open Loop Vector Control

A1-02 = 2

• General variable speed applications
• Applications requiring high precision, high speed control.

PM Open Loop Vector Control

A1-02 = 5

Variable torque applications employing permanent magnet motors

and energy savings.

u

Initialize Parameter Values: A1-03

Parameter A1-03 (Initialize Parameters) resets all parameters to the original default values.

Note:

1. Save all changed parameter settings by setting o2-03 = ”1” before initializing the drive. Settings will

be lost if performing a 2-Wire or 3-Wire initialization using 2220 or 3330 if user parameters are not

saved first.

2. If using Open Loop Vector Control (A1-02 = 2), Auto-Tuning will need to be performed again after

the drive is initialized.

Refer to Auto-Tuning on page 113

for details.

n

Different Methods of Drive initialization

1110: Resets all parameters to user-defined default values

A user-initialization resets all parameters to a user-defined set of default values previously

saved to the drive. Set parameter o2-03 to “2” to clear those values.

Note:

Set o2-03 to “1” to save the current parameter settings and changes for a “user-initialization.” After

saving all parameter setting changes, parameter o2-03 automatically returns to 0. .