B.1 parameter table – Yaskawa J1000 Compact Vector Control Drive User Manual

Page 194

Advertising
background image

H2 Multi-Function Digital Output Settings

H2-

Setting

Function

Description

10

Alarm

Closed: An alarm is triggered.

11

Reset Command Active

Closed: The drive has received a reset command from the multi-function

input terminals or from serial network, or the digital operator RESET

key has been pressed.

12

Timer Output

Timer output, controlled by b4-01 and b4-02. Used in conjunction with

the digital input (H1- = 18 “timer function”).

13

Speed Agree 2

Closed: When drive output frequency equals the frequency reference +/-

L4-04.

14

User Set Speed Agree 2

Closed: When the drive output frequency is equal to the value in L4-03

(plus or minus L4-04).

15

Frequency Detection 3

Closed: When the drive output frequency is less than or equal to the value

in L4-03 with the hysteresis determined by L4-04.

16

Frequency Detection 4

Closed: When the output frequency is greater than or equal to the value

in L4-03 with the hysteresis determined by L4-04.

17

Torque Detection 1 (N.C.)

Open: When the output current/torque exceeds the value set in parameter

L6-02 for more time than is set in parameter L6-03.

18

Torque Detection 2 (N.O.)

Closed: When the output current/torque exceeds the value set in

parameter L6-05 for more time than is set in parameter L6-06.

19

Torque Detection 2 (N.C.)

Open: Output current/torque exceeds the value set in parameter L6-05

for more time than is set in parameter L6-06.

1A

During Reverse Operation

Closed: Drive is running in the reverse direction.

1B

During Baseblock (N.C.)

Open: Drive is in base block condition. Output is disabled.

1C

Motor 2 Selection

Closed: Motor 2 is selected by a digital input (H1- = 16)

1E

Restart Enabled

Closed: An automatic restart is performed

1F

Motor Overload Alarm (oL1)

Closed: OL1 is at 90% of its trip point or greater.

20

Drive Overheat Pre-alarm (oH)

Closed: Heatsink temperature exceeds the parameter L8-02 value.

22

Mechanical Weakening

Closed: Mechanical Weakening detected.

2F

Maintenance Period

Closed: cooling fan, electrolytic capacitors, IGBTs, or the soft charge

bypass relay may require maintenance.

Note: Available in drive software versions PRG: 1016 and later.

30

During Torque Limit

Closed: When the torque limit has been reached.

37

During Frequency Output

Open: No frequency output from drive if stopped, with baseblock, with

DC injection braking during initial excitation, or with short-circuit

braking.

Closed: Drive is outputting a frequency

38

Drive Enable

Closed: Multi-function input closes (H1- = 6A)

39

Watt Hour Pulse Output

Output units are determined by H2-06, outputs 200 ms pulse for each

incremented kWh count.

3C

LOCAL/REMOTE Status

Closed: LOCAL

Open: REMOTE

B.1 Parameter Table

194