H2 Multi-Function Digital Output Settings

H2-

Setting

Function

Description

3D

During Speed Search

Closed: Speed search is being executed.

3E

PID Feedback Low

Closed: PID Feedback Loss.

3F

PID Feedback High

Closed: PID Feedback Fault.

4A

During KEB Operation

Closed: KEB is being performed.

4B

During Short-Circuit Brake

Closed: Short-Circuit Braking is active.

4C

During Fast-stop

Closed: Fast-stop command is entered

4D

oH Pre-alarm Time Limit

Closed: oH Pre-alarm time limit is passed.

4E

Braking Transistor Fault (rr)

Closed: The built-in dynamic braking transistor failed.

Note: Available in drive software versions PRG: 1016 and later.

4F

Braking Resistor Overheat (oH) Closed: The dynamic braking resistor overheated.

Note: Available in drive software versions PRG: 1016 and later.

90 to 92 DriveWorksEZ Digital Output 1

to 3

These settings are for digital output functions used in DriveWorksEZ.

Normally there is no need to change or apply these settings.

100 to

192

H2 Parameter Functions

Reversed Output Switching of 0

to 92

Reverse the output switching of the multi-function output functions. Set

the last two digits of 1 to reverse the output signal of that specific

function.

No.

Name

Description

H3: Analog Inputs

Use H3 parameters to set the multi-function analog input terminals.

H3-01 Terminal A1 Signal Level Selection 0: 0 to +10 V (lower limit)

1: 0 to +10 V (no lower limit)

H3-02 Terminal A1 Function Selection

Sets the function of terminal A1.

H3-03 Terminal A1 Gain Setting

Sets the level of the input value selected in H3-02 when 10V is input

at terminal A1.

H3-04 Terminal A1 Bias Setting

Sets the level of the input value selected in H3-02 when 0V is input

at terminal A1.

H3-09 Terminal A2 Signal Level Selection

Sets the input signal level for terminal A2.

0: 0 to +10 V (with lower limit)

1: 0 to +10 V (no lower limit)

2: 4 to 20 mA

3: 0 to 20 mA

H3-10 Terminal A2 Function Selection

Sets the function of terminal A2.

H3-11 Terminal A2 Gain Setting

Sets the level of the input value selected in H3-10 when 10 V (20

mA) is input at terminal A2.

H3-12 Terminal A2 Bias Setting

Sets the level of the input value selected in H3-10 when 0 V (0 or 4

mA) is input at terminal A2.

H3-13 Analog Input Filter Time Constant

Sets the primary delay filter time constant for terminals A1 and A2.

Used for noise filtering.

B.1 Parameter Table

YASKAWA ELECTRIC TOEP C710606 47C YASKAWA AC Drive – V1000 Quick Start Guide

195

B

Parameter List