T1-01: Tuning Mode Selection

Sets the type of Auto-Tuning to be used.

Refer to Types of Auto-Tuning on page 113

for

details on different types of Auto-Tuning.

No.

Name

Setting Range

Default

T1-01

Auto-Tuning Mode Selection

0, 2 (OLV) 2, 3 (V/f) 0 (OLV) 2 (V/

f)

Setting 0: Rotating Auto-Tuning for Open Loop Vector Control

Setting 2: Stationary Auto-Tuning for Line-to-Line Resistance

Setting 3: Rotating Auto-Tuning for V/f Control

n

T1-02: Motor Rated Power

Used to set the motor rated power according to the motor nameplate value. For optimal

performance, the motor rated power should be between 50 and 100% of the drive rating.

No.

Name

Setting Range

Default

T1-02

Motor Rated Power

<1>

Determined

by o2-04 and

C6-01

<1>

The setting range differs based on drive software version.
PRG: 1016 and later: 0.03 to 650.00 kW
PRG: 1015 and earlier: 0.00 to 650.00 kW

n

T1-03: Motor Rated Voltage (T1-01 = 0 or 3)

Used to set the motor rated voltage according to the motor nameplate value. If the motor is

used above its base speed, enter the voltage at base speed here.
For higher tuning precision and better control performance, enter the motor no-load voltage

here if known. The motor no-load voltage is referred as to the voltage needed to operate the

motor under no-load condition at its rated speed. Refer to the motor data sheet.

No.

Name

Setting Range

Default

T1-03

Motor Rated Voltage

0.0 to 255.5 V

<1>

200.0 V

<1>

<1>

Values shown here are for 200 V class drives. Double values when using a 400 V class drive.

4.7 Auto-Tuning

120

YASKAWA ELECTRIC TOEP C710606 47C YASKAWA AC Drive – V1000 Quick Start Guide