B.1 parameter table – Yaskawa J1000 Compact Vector Control Drive User Manual

Page 179

Advertising
background image

No.

Name

Description

b5-12

PID Feedback Reference Missing

Detection Selection

0: Disabled.

1: Feedback loss detected when PID enabled. Alarm output, operation

is continued without triggering a fault contact.

2: Feedback loss detected when PID enabled. Fault output, operation

is stopped and a fault contact is triggered.

3: Feedback loss detection when PID disabled by digital input. No

alarm/fault output. “PID feedback loss” digital output is switched.

4: PID Feedback error detection when PID disabled by digital input.

An alarm is triggered and the drive continues to run.

5: PID Feedback error detection when PID disabled by digital input.

Fault is triggered and output is shut off.

b5-13

PID Feedback Loss Detection

Level

Sets the PID feedback loss detection level.

b5-14

PID Feedback Loss Detection Time Sets the PID feedback loss detection delay time.

b5-15

PID Sleep Function Start Level

Refer to V1000 Technical Manual for details.

b5-16

PID Sleep Delay Time

Refer to V1000 Technical Manual for details.

b5-17

PID Accel/Decel Time

Refer to V1000 Technical Manual for details.

b5-18

PID Setpoint Selection

Refer to V1000 Technical Manual for details.

b5-19

PID Setpoint Value

Refer to V1000 Technical Manual for details.

b5-20

PID Setpoint Scaling

Refer to V1000 Technical Manual for details.

b5-34

PID Output Lower Limit

Refer to V1000 Technical Manual for details.

b5-35

PID Input Limit

Refer to V1000 Technical Manual for details.

b5-36

PID Feedback High Detection Level Refer to V1000 Technical Manual for details.

b5-37

PID Feedback High Level Detection

Time

Refer to V1000 Technical Manual for details.

b5-38

PID Setpoint / User Display

Refer to V1000 Technical Manual for details.

b5-39

PID Setpoint Display Digits

Refer to V1000 Technical Manual for details.

b5-40

Frequency Reference Monitor

Content during PID

Refer to V1000 Technical Manual for details.

Note: Available in drive software versions PRG: 1014 and later.

b5-47

Reverse Operation Selection 2 by

PID Output

Refer to V1000 Technical Manual for details.

Note: Available in drive software versions PRG: 1020 and later.

b6: Dwell Function

Use b6 parameters to configure dwell function operation.

b6-01

Dwell Reference at Start

Refer to V1000 Technical Manual for details.

b6-02

Dwell Time at Start

b6-03

Dwell Frequency at Stop

b6-04

Dwell Time at Stop

b8: Energy Saving

Use b8 parameters to configure the energy saving/conservation drive function.

b8-01

Energy Saving Control Selection

0: Disabled

1: Enabled (set b8-04)

B.1 Parameter Table

YASKAWA ELECTRIC TOEP C710606 47C YASKAWA AC Drive – V1000 Quick Start Guide

179

B

Parameter List