A.3 three-phase 400 v class drives – Yaskawa J1000 Compact Vector Control Drive User Manual

Page 169

Advertising
background image

Table A.5 Power Ratings Continued

Item

Specification

Three-Phase Model

4A0011

4A0018

4A0023

4A0031

4A0038

Maximum Applicable Motor

Capacity (HP)

<1>

ND Rating

7.5

10.0

15.0

20.0

25.0

HD Rating

5.0

10.0

10.0

15.0

20.0

Input

Input Current (A)

<2>

ND Rating

14.0

20.0

24.0

38.0

44.0

HD Rating

10.4

15.0

20.0

29.0

39.0

Output

Output Current (kVA)

<3>

ND Rating

<4>

8.5

13.3

17.5

23.6

29.0

HD Rating

<5>

7.0

11.3

13.7

18.3

23.6

Output Current (A)

ND Rating

<4>

11.1

17.5

23.0

31.0

38.0

HD Rating

<5>

9.2

14.8

18.0

24.0

31.0

Overload Tolerance

ND Rating: 120% of rated output current for 60 s

HD Rating: 150% of rated output current for 60 s

(Derating may be required for applications that start and stop

frequently)

Carrier Frequency

User-adjustable 2 to 15 kHz

Max Output Voltage (V)

Three-phase power: 380 to 480 V (proportional to input voltage)

Max Output Frequency (Hz)

400 Hz (user-adjustable)

Power

Supply

Rated Voltage

Rated Frequency

Three-phase power: 380 to 480 V 50/60 Hz

DC power supply: 510 to 680 V

<6>

Allowable Voltage Fluctuation

-15 to 10%

Allowable Frequency Fluctuation

±5%

Harmonic Corrective Actions DC Link Choke

Optional

<1>

The motor capacity (HP) refers to a NEC 4-pole motor. The rated output current of the drive output amps should
be equal to or greater than the motor rated current.

<2>

Input current rating varies depending on the power supply transformer, input reactor, wiring conditions, and
power supply impedance.

<3>

Rated motor capacity is calculated with a rated output voltage of 440 V.

<4>

Carrier frequency is set to 2 kHz (Swing PWM). Current derating is required to raise the carrier frequency.

<5>

Carrier frequency is set to 8 kHz. Current derating is required to raise the carrier frequency.

<6>

DC is not available for UL standards.

A.3 Three-Phase 400 V Class Drives

YASKAWA ELECTRIC TOEP C710606 47C YASKAWA AC Drive – V1000 Quick Start Guide

169

A

Specifications

Advertising