Three-Phase 200 V Class

Table 3.3 Wire Gauge and Torque Specifications

Drive

Model

Terminal

Recomm.

Gauge

AWG, kcmil

Wire Range
AWG, kcmil

Screw

Size

Tightening

Torque

N•m (lb.in.)

2A0001

2A0002

2A0004

2A0006

R/L1, S/L2, T/L3

14

18 to 14

M3.5

0.8 to 1.0

(7.1 to 8.9)

U/T1, V/T2, W/T3

14

18 to 14

⊖, ⊕1, ⊕2

18 to 14

B1, B2

18 to 14

14

18 to 14

2A0010

R/L1, S/L2, T/L3

12

14 to 10

M4

1.2 to 1.5

(10.6 to 13.3)

U/T1, V/T2, W/T3

14

14 to 10

⊖, ⊕1, ⊕2

14 to 10

B1, B2

14 to 10

10

14 to 10

2A0012

R/L1, S/L2, T/L3

12

14 to 10

M4

1.2 to 1.5

(10.6 to 13.3)

U/T1, V/T2, W/T3

14

14 to 10

⊖, ⊕1, ⊕2

14 to 10

B1, B2

14 to 10

10

14 to 10

2A0020

R/L1, S/L2, T/L3

10

14 to 10

M4

1.2 to 1.5

(10.6 to 13.3)

U/T1, V/T2, W/T3

10

14 to 10

⊖, ⊕1, ⊕2

14 to 10

B1, B2

14 to 10

10

14 to 10

2A0030

R/L1, S/L2, T/L3

8

10 to 6

M4

2.1 to 2.3

(18.6 to 20.4)

U/T1, V/T2, W/T3

8

10 to 6

⊖, ⊕1, ⊕2

10 to 6

B1, B2

14 to 10

8

10 to 6

M5

2 to 2.5

(17.7 to 22.1)

3.4 Main Circuit Wiring