Yaskawa J1000 Compact Vector Control Drive User Manual

Page 108

Advertising
background image

Drive

A1

A2

Main Frequency Reference
(voltage input)

0 to 10 V

Auxiliary Frequency Reference
(voltage/current input)

AC

Frequency Reference
Common

2 k

W

+ V (+10.5 V, 20 mA)

Figure 4.10 Voltage Input for the Main Frequency Reference

Control Circuit Terminal A2 (Voltage/Current Input):
Use control circuit Terminal A2 when supplying the frequency reference with a current signal

between 4 to 20 mA. Use the following switch and parameter settings to configure Terminal

A2 for 0 to 20 mA or 4 to 20 mA input.

Switching between Main/Auxiliary Frequency References

To configure the frequency reference to switch between analog input A1 and A2 (main/aux

frequency switch), use the following setup:

1.

Set the frequency reference source to terminals (b1-01 = “1”).

2.

Set one of the digital inputs to auxiliary reference 1, H1- = “3” (preset for terminal
S5).

3.

Set input signal type of terminal A2 using dip switch S1 and parameter H3-09.

4.

Set the function of analog input A2 to Auxiliary frequency (H3-10 = “2”).

When the digital input assigned in step 2 is off, terminal A1 is the frequency reference input.

If it is closed, the A2 input value becomes the frequency reference. The active acceleration/

deceleration times are used for the change-over between the values

4.6 Basic Drive Setup Adjustments

108

YASKAWA ELECTRIC TOEP C710606 47C YASKAWA AC Drive – V1000 Quick Start Guide

Advertising