B.1 parameter table – Yaskawa J1000 Compact Vector Control Drive User Manual

Page 191

Advertising
background image

H1 Multi-Function Digital Input Selections

H1-

Setting

Function

Description

10

Up Command

Open: Maintains the current frequency reference

Closed: Increases or decreases the current frequency reference

11

Down Command

12

Forward Jog

Closed: Runs forward at the Jog Frequency d1-17.

13

Reverse Jog

Closed: Runs reverse at the Jog Frequency d1-17.

14

Fault Reset

Closed: Resets faults if cause is cleared and Run command removed.

15

Fast-Stop (N.O.)

Closed: Decelerates at the Fast-Stop time C1-09.

16

Motor 2 Selection

Open: Motor 1 (E1-, E2-)

Closed: Motor 2 (E3-, E4-)

17

Fast-stop (N.C.)

Open: Decelerates according to C1-09 (Fast-stop Time)

18

Timer Input Function

Set the timer delay using parameters b4-01 and b4-02.

19

PID Disable

Closed: PID control disabled

1A

Accel/Decel Time Selection 2 Switches Accel/Decel times.

1B

Program Lockout

Open: Parameters cannot be edited. (except U1-01 if reference source is

set for operator)

Closed: Parameters may be edited and saved.

1E

Reference Sample Hold

Closed: Samples the analog frequency reference and operates the drive at

that speed.

20 to 2F External Fault

20: N.O., Always Detected, Ramp To Stop

21: N.C., Always Detected, Ramp To Stop

22: N.O., During Run, Ramp To Stop

23: N.C., During Run, Ramp To Stop

24: N.O., Always Detected, Coast To Stop

25: N.C., Always Detected, Coast To Stop

26: N.O., During Run, Coast To Stop

27: N.C., During Run, Coast To Stop

28: N.O., Always Detected, Fast-stop

29: N.C., Always Detected, Fast-stop

2A: N.O., During Run, Fast-stop

2B: N.C., During Run, Fast-stop

2C: N.O., Always Detected, Alarm Only (continue running)

2D: N.C., Always Detected, Alarm Only (continue running)

2E: N.O., During Run, Alarm Only (continue running)

2F: N.C., During Run, Alarm Only (continue running)

30

PID Integral Reset

Closed: Resets the PID control integral value.

31

PID Integral Hold

Closed: Maintains the current PID control integral value.

32

Multi-Step Speed Reference 4 Used to select Multi-Step Speeds set in d1-01 to d1-16

34

PID Soft Starter

Closed: Disables the PID soft starter b5-17.

35

PID Input Switch

Closed: Inverses the PID input signal

40

Forward Run Command

(2-wire sequence)

Open: Stop

Closed: Forward run

B.1 Parameter Table

YASKAWA ELECTRIC TOEP C710606 47C YASKAWA AC Drive – V1000 Quick Start Guide

191

B

Parameter List

Advertising