Table c.9, Factory recommended branch circuit protection – Yaskawa J1000 Compact Vector Control Drive User Manual

Page 228

Advertising
background image

The closed-loop crimp terminal sizes and values listed in

Table C.9

are Yaskawa

recommendations. Refer to local codes for proper selections.

Table C.9 Closed-Loop Crimp Terminal Sizes

Wire Gauge

Terminal

Screws

Crimp

Terminal

Model

Number

Tool

Insulation

Cap

Model No.

Code

<1>

Machine No.

Die Jaw

18 AWG

M3.5

R1.25-3.5

YA-4

AD-900

TP-003

100-066-217

16 AWG

M3.5

R1.25-3.5

YA-4

AD-900

TP-003

100-066-217

14 AWG

M3.5

R2-3.5

YA-4

AD-900

TP-003

100-066-218

M4

R2-4

YA-4

AD-900

TP-003

100-054-028

12 / 10 AWG

M4

R5.5-4

YA-4

AD-900

TP-005

100-054-029

M5

R5.5-5

YA-4

AD-900

TP-005

100-054-030

8 AWG

M4

8-4

YA-4

AD-901

TP-008

100-054-031

M5

R8-5

YA-4

AD-901

TP-008

100-054-032

M8

R8-8

YA-4

AD-901

TP-008

100-061-111

6 AWG

M4

14-4

YA-4

AD-902

TP-014

100-66-220

M5

R14-5

YA-4

AD-902

TP-014

100-054-034

M6

R14-6

YA-5

AD-952

TP-014

100-051-261

M8

R14-8

YA-5

AD-952

TP-014

100-054-035

4 AWG

M6

R22-6

YA-5

AD-953

TP-022

100-051-262

M8

R22-8

YA-5

AD-953

TP-022

100-051-263

3 AWG

M8

R38-8

YA-5

AD-954

TP-038

100-051-264

2 AWG

M8

R38-8

YA-5

AD-954

TP-038

100-051-264

<1>

Codes refer to a set of three crimp terminals and three insulation caps. Prepare input and output wiring using
two sets for each connection.
Example: Models with 14 AWG for both input and output require one set for input terminals and one set for
output terminals, so the user should order two sets of [100-066-218].

Note:

Consider the amount of voltage drop when selecting wire gauges. Increase the wire gauge when the

voltage drop is greater than 2% of motor rated voltage. Ensure the wire gauge is suitable for the terminal

block. Use the following formula to calculate the amount of voltage drop:

Line drop voltage (V) = 3 × wire resistance (Ω/km) × wire length (m) × current (A) × 10

-3

n

Factory Recommended Branch Circuit Protection

Yaskawa recommends installing one of the following types of branch circuit protection to

maintain compliance with UL508C. Semiconductor protective type fuses are preferred.
Branch circuit protection shall be provided by any of the following according to

Table C.10

.

• Non-time Delay Class J, T, or CC fuses.
• Time Delay Class J, T, CC, or RK5 fuses.
• Semiconductor fuses.

C.2 UL and CSA Standards

228